Lauda Ultracool UC-0240

Lauda Ultracool UC-0240
Contact us for price
or
Call +1 909-466-7041
Description
Lauda Ultracool UC-0240
ALI Reference #: 106259
details:
- Ultracool UC-0240 SP
- Working temperature min.: -5 °C
- Working temperature max. 25 °C
- Ambient temperature min. -15 °C
- Ambient temperature max. 50 °C
- Temperature stability 2 ±K
- Cooling output at 25°C water outlet temperature 37.3 kW
- Cooling output at 20°C water outlet temperature 34.6 kW
- Cooling output at 15°C water outlet temperature 30.3 kW
- Cooling output at 10°C water outlet temperature 26.3 kW
- Cooling output at 5°C water outlet temperature 22.3 kW
- Cooling output at 0°C water outlet temperature 18.2 kW
- Cooling output at -5°C water outlet temperature 14.5 kW
- Number of refrigeration circuits 1
- Application external
- Power consumption 8 kW
- Pump pressure max. 4.2 bar
- Pump pressure nominal 2.7 bar
- Pump flow max. (pressure) 130 L/min
- Pump flow nominal 84 L/min
- Pump connection thread HT DN25
- Volume water reservoir 100 L
- Dimensions (WxDxH) in mm 715x945x1490
- Noise level 57.5 dB(A)
- Max. fuse 40 A
Specifications
| Manufacturer | Lauda |
| Model | Ultracool UC-0240 |
| Condition | Used |
| Stock Number | 106259 |